AMF controller generator parameters

AMF Controller Generator Parameters

 These two tables contain all necessary AMF controller generator parameters of the BeK3 module. On the left side you see the name of the parameters indicated on the graphic display. Next column indicates the range of the parameters followed by the available options. A short description is provided as well. 

Display Indication

Range

Options

Note

UNDER VOLTAGE      320

BYPASS DELAY         6sec

60

1sec

9990

15sec

OFF

-

Define operating limits for the Generator. If a parameter is out of the limits, the Be-K3 triggers the alarm and can open the KG and stop the engine.

 

Settings of voltages are intended  ‘Phase to Phase’; for single Phase operation voltage is intended  ‘Phase L1 to N’.

 

Under V & Under Hz work only if the contactor of the Generator is closed.

 

The option ON in  [ALTERNATOR FAIL] parameter, will shutdown the engine if the parameters of the Generator are outside of the operating range for at least 300 seconds from engine start.

OVER VOLTAGE          500

BYPASS DELAY         6sec

60

1sec

9990

15sec

OFF

-

UNDER HZ                  47.0

BYPASS DELAY        6sec

20.0

1sec

70.0

15sec

OFF

-

OVER HZ                    53.0

BYPASS DELAY        6sec

20.0

1sec

70.0

15sec

OFF

-

WARNING CURRENT OFF

BYPASS DELAY         6sec

1

1sec

9990

15min

OFF

-

OVER CURRENT        OFF

BYPASS DELAY         6sec

1

1sec

9990

15min

OFF

-

SHORT CIRCUIT         OFF

BYPASS DELAY         0.5sec

1

0.0sec

9990

15.0sec

OFF

-

ALTERNATOR FAIL   OFF

 

               ON or OFF

PHASE MODE           3 PH

 

 

   1PHASE, 3PH, 3PH+CW or 3 CCW

1= single Phase, 3=3 Phases without sequence control. The option CW/CCW controls the requested sequence of Phases. In case of reverse sequence, the engine will shutdown.

           

 

Display Indication

Range

Options

Note

MIN KW LIMIT            OFF

BYPASS DELAY         30sec

10

1sec

9990

59min

OFF

-

To monitor the kW, you can program two outputs with option [10] and [11] (see Table 9.08A). The outputs energize if kW  is outside limits and reset if kW is within limits. A bypass delay should be programmed according to the characteristics of the LOAD.

 

 

MAX KW LIMIT           OFF

BYPASS DELAY         30sec

 

 

10

1sec

 

9990

59min

 

OFF

-

 

KVA SHUTDOWN     OFF BYPASS DELAY        30sec

 

10

1sec

 

9990

59min

 

OFF

-

 If the power rises above the [KVA SHUT DOWN] limit for at least the [BYPASS DELAY] time, the Be-K3 opens the contactor and shuts down the engine, The  OFF setting (>9990KVA) disables the alarm.

 

REVERSE POWER    OFF

BYPASS DELAY         1sec

10

1sec

9990

15sec

OFF

-

If kW1 (or 2, 3) becomes negative and exceeds the limit, the KG opens and the engine will shutdown after a cooling down time.

PHASE UNBALANCE

                                     OFF

BYPASS DELAY        

                                      15sec

10

 

1

999

 

59sec

OFF

If the difference of voltage between phases rises above the setting, the KG opens and  the engine will shutdown after a cooling down time. The option  OFF disables the Unbalance monitoring.

EARTH FAULT         OFF

BYPASS DELAY       1.0sec

0.1

0.3sec

99.9

10sec

OFF

-

Provides Earth Fault current (or Differential Protection) Monitoring.

CT SIZE L1 L2 L3        500

    5

 

 9990

 

       -

It defines the sizes of the C.T. for the phases L1-2-3 of the Generator.

CT SIZE EARTH          100

 

    5

 

 9990

 

       -

 

It defines the size of the C.T. for the Earth Current

 

VAC RATIO                1.0

1.0

15.0

-

It extends the reading range of the Vac up to 9990Vac

(in this case a voltage transformer is mandatory)

 

AMF controller generator parameters

In addition to the AMF controller generator parameters, the BeK3 allows you to set up the under speed protection. It works in this way. After starting the engine, the BeK3 will close the generator circuit breaker. This will happen supposing the generator parameters are  stable within the setting limits. Once the generator circuit breaker is closed, if the rotational speed (the measurement is provided by a pick-up of mathematically calculated from the frequency) falls under the 'Under Speed' limit for a pre-configured time, the BeK3 AMF controller will open the generator circuit breaker and will shut down the engine following a pre-set cooling down time. You can set up the Under speed protection in the 'ENGINE PARAMETERS' menu of the Bek3.

 

AMF Controller Generator Parameters &amp