BE124 CENTURION
The BE124 CENTURION is able to monitor a generator with the following characteristics:
- VOLTAGE 60Vac up to 600Vac - FREQUENCY 25 up to 600HZ
- CURRENT 0 up to 2000Aac - SINGLE PH / 2-PH / 3-PH
You can set up protective functions about Over/Under Voltage, Over/Under Frequency, Over KVA, Reverse Power, Phase Unbalance, Phase Sequence, Alternator Failure, Earth Fault & Short Circuit. You can connect any type of engine.
BE124 CENTURION STARTER CONNECTION
This is the basic arrangement for a simple AUTO START. You are required to use a relay [2] to drive an 'energized to run' FUEL SOLENOID and a pilot relay [3] for the starter motor [5]. You are required to use cable of proper size [4]. The Be124 continuously monitors the W.L. terminal of the belt alternator [1] to terminate the crank at the proper moment. If necessary, you can set up programmable outputs for PRE-GLOW, CHOKE or GAS SOLENOID.
BE124 CENTURION CONFIGURABLE OUTPUTS
This is the typical connection for output relays. The BE124 outputs are short circuit proof. The logic is positive. You are required to use automotive relays in accordance to the battery voltage (e.g. 12V relays for a 12V battery, 24V relays for a 24V battery). It is mandatory to use diodes in parallel with the relay coils ([2]). You are required to connect the other side of the coil to a solid battery minus (normally grounded). We recommend that you protect with fuses the contacts of the relays ([3] / [4]).

BE124 CENTURION CONFIGURABLE INPUT
The BE124 Centurion is extremely flexible, especially on adjustable input point of view. You can use 3 inputs in analog/digital mode and 3 inputs in digital mode only. For each input you can configure up to 15 different options that include warning functions or shutdowns. You can choose also the option N.O. or N.C.. For the analog inputs you can configure any kind of response curves. An embedded troubleshooting will allow you to monitor on-site the status of each input.
BE124 CENTURION POWER SUPPLY
A good battery connection is the secret of a long term reliability of a generator AUTO START. A powerful battery will be useless without good wiring.
The basic rules are simple: -Proper size for each cable -A solid connection -Only one common ground point -Always use diodes in parallel to coils

BE124 CENTURION CANBUS & MODBUS
BE124 features an RS485 serial interface that supports the MODBUS-RTU protocol. You can download our free of charge software for control and monitoring.The embedded serial interface is able to drive a twisted cable of about 1000 m.
BE124 features an CANBUS serial interface in a way that you can connect engines with a SAEJ1939 compatible ECU. The CANBUS port is fully isolated and protected by reverse voltage.
BE124 CENTURION SPECIFICATIONS
Supply Voltage: 5.5Vdc to 36Vdc, 10-150mA max. Fuse: internal 300mA electronic. Reverse polarity: -36Vdc
Supply Voltage Surge Protection: 100Vdc /500 Amps (8/20 microseconds). Absorption capacity: 8 Joule max
Cranking Dropout: Be124 survives 0V for a half-second (initial voltage before the dropout: 12Vdc).
Dimensions: 96mm X 96mm X 87,5mm. Panel Size Cut-out: 91mm X 91mm, indoor operation
Operating Temperature Range: -25 deg. C up to +70 deg. C. Humidity Range: 5% up to 95% non-condensing.
Weight: 550 grams. General design: ECC 89/336, 89/392, 73/23, 93/68, IEC 68-2-6. Certification: CE
Static Outputs Characteristics
positive logic with 150mA output current (Vbatt - 1Vdc), short circuit proof.
Generator Voltage
nominal voltage 70 Vac up to 600Vac (Ph-Ph) 347Vac (Ph-N). Over voltage: 4KVac Ph-Ph. Measurement precision (V/Hz): +/- 1% F.S.. Impedance: 2 M Ohm. Resolution: 1Vac .
Generator Frequency
nominal frequency 20.0 Hz up to 600.0 Hz. Measurement precision: +/- 1% F.S..
Impedance: 2 M Ohm. Resolution / Accuracy: 0,1Hz (20.0-600.0Hz).
Current Sensing
5/5Aac up to 2000/5Aac. Maximum permanent current on the sensing inputs: 7Aac.
Measurement precision: +/- 2%. Internal resistance: 0.05 Ohm. Resolution 0,1Aac (<500/5), 1Aac (>500/5).
Digital Inputs
open circuit voltage of approximately 4,5V - Trigger level: < 2Vdc (max 5mA).
Maximum Overvoltage +/-100V 1 s. Permanent short circuit to Bt+ and Bt- allowed for unlimited time.
Analogue Inputs
resistance range 0 up to 1000Ohm. Current at zero Ohm: 5mA. Overvoltage +/-100V. Accuracy: 2%.
Charger Alternator Monitoring
operating voltage up to 36Vdc/3W. Vdc reading accuracy +/- 2%.
Magnetic Pickup Input
0,5V-50VRMS, 10-25KHz. RPM reading accuracy +/- 1%. Teeth Count: 10.0/500.0.
CAN Port
fully isolated. 250Kb/second. Internal 120 Ohm impedance available for connection. Supports SAE1939 protocol.
RS485 Port
support Modbus Protocol and drives 1000 Metres twisted cable, ESD 2KV & drives up to 127 nodes.