FIRE PUMP CONTROLLER ALARM MANAGEMENT

FIRE PUMP CONTROLLER ALARM MANAGEMENT

This menu can contain up to 10 pages of active alarms tagged with date and time. It is possible to record up to 200 pages of historical events. A typical alarm page is indicated below:

 

Typical alarm page (to enter this page, in case of an alarm, push [ACK])

 

ALARM   PAGE      1/10   

LOW OIL PRESSURE

SHUTDOWN    0,8 BAR

DD/MM/YY   HH:MM:SS

 

ALARM   PAGE      2/10   

LOW OIL PRESSURE

WARNING     2,8 BAR

DD/MM/YY  HH:MM:SS

This page opens automatically in case of alarm(s). Use [ ↑ ] or [ ↓ ] to browse the content of the pages. The alarms are also recorded in the Event History memory. To open the pages of the Event History repeatedly push the [ ↓ ] pushbutton. To exit the alarm page, push [ACK]: you open the ‘Be126 Status’ page (see 5.0).

 

The Be126 records up to 500 events. It indicates date & time information for warnings, shutdowns and other events. Use [ ↑ ] or [ ↓ ] to browse the content of the pages. Push [ACK] to exit and open the ‘Be126 Status’ page.  If no one single alarm is active the screen indicates the message [NO ALARMS] .

 

Note:  to remove the alarm from the page, see section ALARM MANAGEMENT.