Fire Pump Controller Clear Memory

Fire Pump Controller Clear Memory

To enter this menu, push the [OFF] button to enter the [OFF] mode of operation. Push the [MENU] button to open the Main Menu. Use [ ↑ ] or [ ↓ ] to navigate and select the [CLEAR MEMORY] menu. Push [→] to enter the menu.This command allows you to clear the all memory. The Be126 will use the defaults parameters.

Display

Instructions for clearing the memory

 

 

    

CLEAR MEMORY?

[] YES          NO  [→]

HOLD LEFT          5SEC

 

 

 

CLEAR MEMORY

              DONE

 

 

A) - Push the [] pushbutton for at least 5 seconds to cancel the memory; a count down will appear on display before triggering the function.

 

B) - You can quit the procedure at any time by pushing [→]  (you exit the function).

 

C) - After writing the factory settings, the display confirms the operation via the message [CLEAR MEMORY DONE].

 

Note: we recommend that you remove the supply for a few seconds. After reconnecting the supply check the parameters. The programming of some parameters may be required according to your application.