FIRE PUMP CONTROLLER DATA COMMUNICATION

FIRE PUMP CONTROLLER DATA COMMUNICATION

Display

Description

 

MODBUS CB1

                                 OFF

MODBUS CB2

                                  OFF

 

BE126 NODE

                                 3

This menu allows you to set up the MODBUS data communication for the battery chargers.

Default settings provide ‘NO MODBUS’ battery charger. In NFPA/EN applications we recommend that you set MODBUS 1 & 2 to ‘ON’. In this way you can connect a Bernini Design NFPA/EN compliant battery charger. ‘Battery Charger 1’ features a NODE 1. ‘Battery Charger 2’ features a NODE 2. You are required to wire the battery chargers accordingly (Connect ‘Battery Charger 1’ to battery set ‘1’ & ‘Battery Charger 2’ to battery set ‘2’). Default MODBUS node for BE126 is ‘3’. The nodes 1 & 2 are reserved for the battery chargers. In case you enable a battery charger MODBUS, you are no longer allowed to setup a [BE126 NODE] to 1 or 2 for the BE126.