Fire Pump Controller Digital Inputs

Fire Pump Controller Digital Inputs

To enter this menu, push the [OFF] button to enter the [OFF] mode of operation. Push the [MENU] button to open the Main Menu. Use [ ↑ ] or [ ↓ ] to navigate and select the [SWITCHES TEST] menu. Push [→] to enter the menu.This menu displays the name of the terminal that you activate.

 

 

Display
  
Fire Pump Controller Digital Inputs Test Instructions

 

SWITCHES TEST

JF1                         JF7

JF2                         JF8

JF3                         JF9

JF4                         JF10

JF5

JF6

 

 

 

When you connect a digital input to the battery minus, the display indicates the name of the connection. When all inputs are ‘open’ (not connected to battery minus), the display must indicate only the message [SWITCHES TEST]. Activating one by one the inputs, the display indicates the name of the connection. If you activate all inputs, the screen indicates all connections. If you activate one input and the display indicates two messages, this mean a presence of a short circuit.