Fire Pump Controller Digital Outputs

Fire Pump Controller Digital Outputs

To enter this menu, push the [OFF] button to enter the [OFF] mode of operation. Push the [MENU] button to open the Main Menu. Use [ ↑ ] or [ ↓ ] to navigate and select the [OUTPUTS TEST] menu. Push [→] to enter the menu.This menu displays the measurements made on the analog inputs.

Display

Fire Pump Controller Digital Outputs Test Instructions

 

OUTPUTS TEST

KEY UP/DOWN SELECTION

KEY RIGHT OUTPUT ON

JC1

PREGLOW

 

 

 

WARNING: THIS PROCEDURE MUST BE CARRIED OUT BY QUALIFIED PERSONNEL ONLY. THE ENGINE MAY START OR YOU CAN INADVERTENTLY ACTIVATE  A WRONG OUTPUT

 

The output troubleshooting is menu driven. By using the [ ↑ ] or [ ↓ ] you select an output. By pushing and holding the [→] button, you activate the output. The display indicates the terminal and the name of the connection. In case you use a lamp to test the output, we recommend that you not exceed 3W (either 12V or 24V).