Fire Pump Controller Push Buttons Test

Fire Pump Controller Push Buttons Test

To enter this menu, push the [OFF] button to enter the [OFF] mode of operation. Push the [MENU] button to open the Main Menu. Use [ ↑ ] or [ ↓ ] to navigate and select the [PUSHBUTTONS TEST] menu. Push [→] to enter the menu.This menu displays the name of the push button that you activate.

Display

Fire Pump Controller Push Buttons Test Instructions

 

PUSHBUTTONS TEST

RIGHT          DOWN

                     START1

                     START2

                      TEST

UP                 LEDS

 

Note: [OFF], [MAN] and [AUTO] push buttons are working all time (if you push [AUTO], the Be126 will enter the AUTO mode).

To exit, push the [ACK] button.

 

WARNING: THIS PROCEDURE MUST BE CARRIED OUT BY QUALIFIED PERSONNEL ONLY. THE ENGINE MAY START OR YOU CAN INADVERTENTLY ACTIVATE  SOME FUNCTIONS.

 

The purpose of this tool is to test the efficiency of the push buttons. Normally, without any push button pressed, the display must indicate the only message  [PUSHBUTTONS TEST]. On the left side you can see the position of the messages.

 

Please note: if you push the [OFF] or [MAN] or [AUTO] (supposing the button is working) you will get a change of mode of operation. In other words, these push buttons are always active. The [START1] & [START2] pushbuttons trigger only a message on the display.