To program a Fuel Parameter follow the instructions

The fuel settings are included in the OEM menu. You can set warnings and shutdowns according to your needs.

> Turn the key to OFF position

> Repeatedly push [←] until the message  [ENGINE METERING]  appears on the top of the display.

> Repeatedly push [ ↓ ] to select the function [OEM PARAMETERS].

> Push [→], the following options will appear on the screen:

[READ PARAMETERS] [MODIFY PARAMETERS] [ENGINE TYPE]

> Push [ ↓ ] to select [MODIFY PARAMETERS] then push [→] to open the list.

> Push [ ↓ ] to select [FUEL PARAMETERS] then push [→] to open the list of the settings.

The video on the right will help you in carrying out a programming task. We recommend that you limit the access to the parameters by using a Password.

 

Generator Controller Fuel Settings

 

ADJUSTABLE FUEL PARAMETERS LIST 

Use the [ ↑ ] or [ ↓ ] arrow to select a parameter. Push the [→]  push button to enter the numerical field. Push the [ ↑ ] or [ ↓ ] arrow to set a value. Push the [←] push button to return to the parameter list; in case you modify a parameter, the Be124 will automatically the page with the instructions about saving the settings.

Fuel Parameters

Notes

Fuel Parameters

Notes

 

TANK EMPTY LEVEL                       

                             OFF

TANK EMPTY DELAY

                             OFF

(1-99%

/15s-59mins-OFF)

The engine shuts down if the level drops below the [TANK EMPTY LEVEL] limit or over the [TANK EMPTY DELAY] time. Be124 monitors a sensor or switch connected to input JC-5 (note 1). Set to 'OFF' to disable the shutdown; it will trigger a FUEL RESERVE warning only.

 

TANK PUMP START                       

                            OFF

TANK PUMP STOP

                            OFF

(limits 1-99%)

Program an output with option [13] (table 11.9) to drive a pump to fill the tank. A delay of 15 seconds for the start and stop of the pump is provided.

 

 

The Be124 disables the pump if the [TANK FILL TIME] time is exceeded. An timeout alarm is also  provided. The pump is disabled when you turn the key to OFF.

 

LOW FUEL WARNING                   

                             OFF

HIGH FUEL WRN

                             OFF

(limits 1-99%)

Be124 monitors the fuel level providing a warning, by programming at least one limit, you enable the JC-5 to work with a sensor (see note 1) and you will obtain a reading on the display.

 

TANK FILL TIME

                            OFF

(15s-59mins-OFF)

 

(Note 1) If a fuel sensor is not available, you can connect a 'Fuel Level Switch' to Input JC-5; you have to ensure the OFF settings are enabled on  [TANK EMPTY LEVEL], [LOW FUEL WARNING] & [HIGH FUEL WRN] in a way to configure the input in 'digital' mode.  In addition to a level monitoring via 'Resistive Sensor' connected to JC-5, you can configure one programmable input (JC10-9-8) with option [10] (see 11.8 of the OEM manual) and connect a 'Fuel Level Switch'. The timer [TANK EMPTY DELAY] starts to count when the 'Fuel Level Switch' closes its contacts. The engine shuts down when the timer expires. If you set the [TANK EMPTY DELAY] into [OFF] mode, the Be124 generates only a warning. The section 23.6 of the OEM manual provides additional information about the Fuel Level alarms.