Be26 Diesel Fire Fighting Pump Controller

THE BE26 WAS FIRSTLY INTRODUCED IN 1990. THIS ITEM IS AVAILABLE ONLY ON REQUEST. FOR NEW APPLICATIONS WE RECOMMEND THAT YOU INSTALL THE

NFPA20 COMPLIANT CONTROLLER BE126

Diesel Fire Fighting Pump Controller

PURCHASE ONE PIECE

799€

Free Shipping

BE26A Controller Rear View
 The BE26 controller is suitable for diesel-engine driven pumps used in fire-fighting applications. The BE26A complies with NFPA-20 regulations. For new applications, we recommend that you use the most advanced

BE26 INSTALLATION MANUAL


BE26 AUTO MODE OF OPERATION

The engine starts in 'AUTO' in case of low water pressure. A programmable delay is provided by an adjustable parameter. The BE26A initiates the start when the Pressure Switch opens. The engine will continue to run independently of the pressure switch status. In AUTO mode, it is possible to START the engine without delay by using a REMOTE TEST switch. The engine stops when the contact of the REMOTE TEST switch opens. The Pressure Switch has priority over a REMOTE TEST.


BE26 MANUAL MODE OF OPERATION

  To control the engine in manual, use the 'START' and 'STOP' pushbuttons. To select the MANUAL mode, turn the Key-Switch into MAN. In accordance with the NFPA-20 standard, it is not possible to remove the key in MANUAL mode. The STOP button is always disabled in NFPA-20 MODE. To stop the engine, turn the key to OFF  mode.


BERNINI DESIGN SRL

Zona Industriale,

46035 Ostiglia,  Italy

 [email protected] 

 support 0039 335 7077148