solar battery GSM remote monitoring

SOLAR BETTERY GSM REMOTE MONITORING RELAY

A STEP-BY-STEP SET-UP GUIDE

USB CONFIGURABLE UP TO 500V

 HIGH PRECISION   

STATIC & RELAY OUTPUTS 

  RAIL MOUNT

USER-FRIENDLY SMS INTERFACE

ADJUSTABLE BATTERY MONITORING RELAY

The Be248 solar battery GSM monitoring relay is the ideal choice when it is for critical applications.  The embedded software driver is compatible with all operating systems.  Measurement precision of Be248 solar battery GSM monitoring relay can be calibrated down to 0% error via USB connections.

The Be248 DC solar battery GSM monitoring relay, in addition to the SOLAR BATTERY PACK voltage monitoring, offers battery voltage monitoring of the engine battery (usually 12V or 24V). You can set up the automatic start of the generator in order to prevent low battery voltage. A set of programmable parameters allows you to set Voltage Thresholds, delay timings, and time-out timing. You can easily interface the Be48 with the most popular auto-start modules.

BATTERY MONITORING RELAY CIRCUIT DIAGRAM

You can supply the BE248 by using a DC source in between 8 up to 30 Vdc connected to terminals JA1-2 via a protection fuse [6]. The JA3-4 terminals can deliver an electronically limited 300mA current [7]. The inputs JA1-2 are protected from reverse polarity for an unlimited time. For battery voltage monitoring connect terminals JF2-3 to a voltage between 0VDC to 100VDC via a protection fuse. Does not matter the polarity. If your battery is over 100Vdc, we recommend that you use the terminals JF1-4. Again, polarity does not matter. You can connect the terminals JD3-4 to drive an alarm indicator and use terminal JD1-2 to activate a power generator [5] via its own auto start module [4].

LIFETIME WARRANTY

BE248 SOLAR BATTERY GSM MONITORING RELAY INSTALLATION MANUAL

 [email protected]

24-7-365 SUPPORT +39 335 70 77 148

 

ONE SAMPLE

E.U. & AMERICA

FREE SHIPPING

248€

 

 

 


 HOW TO SUPPLY THE VOLTAGE MONITORING RELAY

The basic goal of the relay is to keep healthy your battery pack. In other words the relay will instruct the generator to start. The easiest way to supply the relay is to use the battery of the engine. The Be248 does not consume precious current from the battery pack. For this reason a good compromise in price is obtained by designing the supply at maximum 30Vdc. In particular cases, the 12V or 24V source is unavailable for some reason. If you have a source that exceeds the 30V, we recommend using a DC-DC adapter with 12V or 24V output. We recommend that you use our accessories 30-75Vdc/12Vdc/1A (input range 30-75Vdc).

 

30-75Vdc/12Vdc/1Adc

RAIL MOUNT CONVERTER

ONLINE PURCHASE

 49€


In some rare cases, there is high-voltage battery storage. In this case, we offer the option for a wide range of power supply DC-DC converters up to 400Vdc. Contact us for additional information

100-400Vdc/12Vdc/1A

RAIL MOUNT CONVERTER

ONLINE PURCHASE

SUPPORT

0040721241361

 99€

 


 

SETTING UP THE VOLTAGE MONITORING RELAY

Before placing the BE248 SOLAR BATTERY GSM MONITORING RELAY into your system, you are required to set up the adjustable parameters. Factory defaults set the BE248 in 'NON-OPERATIVE' mode. This means that when you apply the DC supply, you will not get output relays functionality.

PRELIMINARY OPERATIONS

We provide free of charge software that allows you to set up the relay.  You will obtain the link to the software after you purchase a BE248 relay. The Be248 monitoring relay is supplied with a 1-meter long USB cable fitted with USB TYPE ‘A’ on one side, suitable for a computer, and a UBS TYPE ‘B’ suitable for Be48 on the other side. See the picture.

!! CAUTION !!

Make sure that the SUPPLY MINUS you use for the Be248 is at the same potential as your computer. The best safety condition is obtained when the terminal minus of DC supply is grounded. Another option is to use a battery of 12V or 24V or to use a normal isolated power supply. To avoid electric shock verify that there is no significant voltage between the supply minus and the shell of your USB cable.

STEP 1 USB CONNECTION

- Provide a DC supply in the range of 10..30Vdc capable of supplying at least 200mA.

- Choose the power supply according to the above-mentioned characteristics.

- Turn OFF the supply.

- Connect DC supply plus to terminal JA1 and DC supply minus to terminal JA2.

- Activate the DIP-SWITCH number 3 down to its 'ON' position; this will disable the USB PORT.

- Turn on the DC supply; the Be248 will turn on all LEDs for a second.

- The GREEN LED DL1 turns on indicating that controller is ready; other LEDs may turn on if Be248 has some previous settings.

- Connect the USB cable to the computer and Be248.

- Start the application 'BE248 DC Voltage Monitoring' on your computer.

- When the red message ‘CONNECTING..’ appears on the screen, turn to ‘OFF’ the DIP-SWITCH number 3; this operation enables the USB PORT communication.

- The computer screen will indicate. on the top left corner, the green message ' CONNECTED'.

STEP 2 UNDERSTANDING THE CONFIGURATION SOFTWARE

The software in addition to offering the battery system measurement features power supply indication and a set of adjustable settings. There you are an overview of the screen.

BE48 DC VOLTAGE MONITORING SCREEN

[1] Battery voltage measurement [2] Thresholds settings  [3] Timing settings [4] Mode of operation [5] Main buttons

STEP 3 VOLTAGE SETTINGS

'Low Voltage Start' is the voltage level of the battery that triggers the timer 'T1' (once 'T1' expires, the output relay turns on). 'High Voltage Stop' is the voltage level of the battery that triggers the timer 'T2' (Once 'T2' expires, the output relay turns off).

Set 'Low Voltage Start' and 'High Voltage Stop' according to your needs by using the mouse over the up/down arrows.

To guarantee stability we recommend that you maintain a minimum difference of at least 2 V between 'Low Voltage Start' and 'High Voltage Stop'. 'High Voltage Stop' must always be set higher than 'Low Voltage Start'.

STEP 4 TIMING SETTINGS

START & STOP delay timers are used to provide flexibility to your application. You can use these timers to avoid false start and stop commands. As a matter of fact, the voltage comparator itself has a fast response and may cause system instability.

 

In this example, the output relay turns on after one minute (T1) and turns off after 30 minutes (T2). You can put the timers to zero when  Be248 is used in particular applications. The range of the timers spans from one second up to 24 hours. This picture makes it clear.

 

STEP 5 THE BASIC COMMANDS

The basic available commands are SAVE (to store a parameter), DEFAULT (to use factory settings), and RELOAD (it cancels a modification and restores the previous setting). If you modify a parameter, a yellow background will warn you. Once stored in the memory the yellow background will disappear

STEP 6 OPTIONAL TIMEOUT SETTING

UNDER OVER VOLTAGE TIME RELAY

This additional timer is extremely important when you want to add security to your system. If there is a failure on the charger, you will never be able to charge the battery or you will risk overcharging it. This timer limits, for example,  the run time of the engine. Once the BE248 triggers the alarm, you are required to remove the DC power supply by removing the JA plug for a few seconds. This will reset the alarm.

MONITORING RELAY TIME OUT

STEP 7  OPTIONAL VOLTAGE CALIBRATION

WARNING!

CAUTION!

PAY ATTENTION TO THE COMMON GROUND LOOP WHEN YOU CALIBRATE FOR A BATTERY OVER 60VDC. YOU MAY DAMAGE YOUR COMPUTER. HIGH DC VOLTAGES MAY BE EXTREMELY DANGEROUS. THE CALIBRATION PROCEDURE MUST BE CARRIED OUT BY QUALIFIED PERSONNEL ONLY. WE RECOMMEND THAT YOU PUT PROTECTION FUSES ON THE BATTERY SIDE

The factory precision of the measurements is about 1%. If you want more precision, we recommend that you carry out the calibration. Use a precise measurement instrument for the battery and you will take note of the measurement. Push the button [Calibration]. Choose the proper range: 60V or 300V according to your measurement. Use up and down to match the measurement and then push the button 'SAVE'. The Be248 will calculate the correction factor. You will get in a few seconds the reading with approximately 'NO ERROR'. A good calibration will allow you a 0,1% accuracy. The calibration is stored in a NON VOLATILE memory.

DC VOLTAGE LOGGER

If you want to carry out really accurate testing of the system, the BE248 provides a real-time data logger. By analyzing the TIMESTAMP you can find out if the system works as you expect. To make LOG HISTORY perform accurately you are required to maintain your computer connected to the BE248 monitoring relay. We recommend that you use a fully isolated USB repeater. Using normal cable extenders you can cover distances up to 20 meters without problems.

VOLTAGE MONITORING RELAY LOG EVENTS

BE248 LED INDICATORS AND DIP-SWITCH

The DIP SW 1 and 2 are not used in the standard version. The DIP3 is momentarily used to enter the configuration procedure.

The DIP4 activates the comparator output relay. You can use it to make a test. As long as the switch is activated (on) the DL4 will continuously blink.

The DL1 green indicator turns on when the CPU is running. It blinks fast when the DC supply is lower than 8Vdc for at least 5 seconds. In this case, the Be48 turns continuously on the red LED indicator DL5.DC Supply: 5.5/36Vdc, 50/150mA

The DL2 yellow indicator blinks slowly when the battery voltage is lower than the threshold. It blinks fast when the battery voltage is over the threshold. It remains lit when the voltage is within the settings

BE48 LED INDICATORS

The DL3 yellow indicator is normally off. It blinks when the Be248 activates a timer T1 or T2

The DL4 yellow indicator turns on when the output relay JD1-2 is energized. It turns off when the relay output is off. It blinks fast when the BE248 is in TEST MODE (DIPSW4 is in its ON position).

The DL5 red indicator turns on in case of alarm time-out (it energizes the relay alarm and de-energizes the relay comparator output)

 The DL5 turns on when the DC falls below 8VDC for at least 5 seconds. The alarm auto resets when the voltage rises above 8Vdc.

BE248 SPECIFICATIONS

DC Supply: 5.5/36Vdc, 50/150mA

Aux supply output: 600mA @ DC Supply-0.5V

Protection: 300mA thermal fuse

Dimensions:: 110 X 120 X 22 (mm)

DIN RAIL mount

Operating temperature: -25 deg C up to +70 deg C

Humidity range: 5% up to 95%

Weight: 130 grams

Meets ECC 89/336, 89/392, 73/23, 93/68, IEC 68-2-6

Certification: CE

Yellow LED Indicators: 3

Red LED Indicator: 1

Green LED Indicator: 1

DC Relay Outputs: 1A 30VDC.

AC Relay Outputs: 5A 250V  AC

Connectors: removable terminal blocks

Battery monitoring Vdc: 5-500Vac

Configuration via USB

Battery monitoring Vdc: 5-400Vdc